JET 340 M
Air heater, 26 kW + Modbusrouter
- Applicable in high areas with 5 to 15m height
- Sustainable heating solution
- Low investment costs
- Provided with Modbusrouter
- Reduces heat loss through the ceiling
Description
The Winterwarm JET-M 340 is an air heater with a capacity of 25,5 kW at water temperatures of 35°C/30°C. Higher water temperatures (f.i. with district heating) provide a higher heat output.
Attention: when the temperature of the discharged air gets higher, the throw is reduced!
The adjustable nozzles have an inducing discharge pattern with a wide spread in the area and an optimal warmth distribution. For this reason extra destratification fans are not required anymore.
Features
- Applicable in high areas with 5 to 15m height
- Heating with low water temperatures
- Suitable for application with heat pump or district heating
- As standard provided with Modbus router
- Control by means of a Building Management System or Smart Controller
- User-friendly operation with readable performance
- Conical nozzles with induction of air n
- High comfort level
- No extra recirculation fans needed
Technical features
| Material heat exchanger | Aluminium/copper |
|---|---|
| Heat emission | 0kW - 25.5kW |
| Fan type | Axial |
| Suitable for wall mounting | No |
| Suitable for in-roof mounting | Yes |
| Suitable for floor mounting | No |
| With suspension | No |
| Air volume | 0m³/h - 8000m³/h |
| Max. throw horizontal | 0m |
| Max. throw vertical | 16m |
| dT heating air | 15K - 30K |
| Connection voltage | 230V - 230V |
| Number of phases | 1 |
| Nominal current | 1.8A |
| Max. electric power input | 1100W |
| Sound pressure level at height of 5 metres | 53dB(A) - 69dB(A) |
| Adjustable induction in exhaust air | No |
| Adjustable fins on exhaust side | Yes |
| Height | 920mm |
| Width | 895mm |
| Depth | 865mm |
| Free-exhausting | Yes |
| Connection | External thread conical BSPT-R (ISO 7-1 / EN 10226-1) |
| Nominal diameter | 1 inch (25) |
| Water-side resistance at dT 20 °C | 30kPa |
| Max. operating pressure | 500kPa |
| Water content | 6.6l |
| Weight including filling | 93kg |